资 源 简 介
A new cable fault location method based on
wavelet reconstruction is proposed. In this method the
difference between the currents of faulty phase and sound
phase under the high voltage pulse excitation is used as the
measured signal and is decomposed in multi-scale by wavelet
transform, then reconstructed in single scale. Comparing with
traditional fault location method by travelling wave, the
presented method will not be interfered by the reflected wave
from the branch joint of cables or from other positions where
the impedances are not matched and not be influenced by fault
types, otherwise, the reflected waves can be recognized even
the faulty position is near to the measuring terminal, at the
same time, the influence of the wave speed uncertainty can be
reduced. The correctness of the proposed method is proved by
simulation results.